The SPD is mainly used for lightning or other transient overvoltage surge protection of
low-voltage power supply and distribution system and electrical equipment.
The product is mainly used for the first level lightning protection of a three-phase AC power supply
system, and the multilayer graphite gap of trigger circuit is used internal.
| Item | Specification |
| Product model | HM385-25T1(3P+N) |
| SPD type | Class I |
| Nominal operating voltage-Un | 230~400VAC |
Max. continuous operating voltage-Uc | 385VAC |
| Response time-ta | 100ns |
| Nominal discharge current-In(8/20μs) | 25kA(L-N);60kA(N-PE) |
| Impulse current-Iimp(10/350μs) | 25kA(L-N);60kA(N-PE) |
Voltage protection level-Up | 2.5kV(L-N);1.5kV(N-PE) |
| Short-circuit current withstand | 10kArms |
| Rated disconnected continuous current value-Ifi | 1.5kArms(385VAC)/6kArms(275VAC)(L-N) |
| Rated disconnected continuous current value-Ifi | 100kArms(255VAC)(N-PE) |
| Transient short time overshortage characteristics-UTOV | 442V/5sec(L-N);1200V/200ms(N-PE) |
| Max backup fuse | 315A gL/gG |
| Size for terminal connection | 6m㎡~25m㎡ (flexiblility)/35m㎡ (inflexibility) |
| Shell fire retardant grade | UL94 V-0 |
| IP grade | IP20 |
| SPD enclosure material | PA 66+30% Glass fiber, PANTONE 426C |
| Working Temperature | -40℃~+85℃ |
| Store Temperature | -40℃~+85℃ |
| Relative Humidity | 5%~95%(25℃) |
| Height above sea level | ≤4000m |